第二個(gè)機(jī)架只需要5伏電源,兩個(gè)機(jī)架所需的總功率與電源容量有關(guān)。第二個(gè)機(jī)架消耗的電流小于5.2安培。兩個(gè)機(jī)架必須緊密安裝受可用3英尺連接電纜的限制。用于雙機(jī)架操作的連接電纜為表1中列出了訂購信息。該電纜車包括+5伏電源總線和電源對信號(hào)進(jìn)行排序。它使用9針D型連接器它通過一個(gè)機(jī)架中的開口。注意,電纜承載僅限功率和功率排序信號(hào)。機(jī)架間通信和總線接口模塊必須單獨(dú)提供。參見適用的可編程控制器安裝手冊。有關(guān)應(yīng)用程序信息。系統(tǒng)重置。5VSTBY輸出可用于用戶電池備份方案如圖所示。通電時(shí),ACFAIL信號(hào)出錯(cuò)5伏總線在規(guī)格范圍內(nèi)后不久。SYSRESET將系統(tǒng)保持在重置狀態(tài)至少5伏電源可用后200毫秒(期間這一次,輸出被強(qiáng)制關(guān)閉)。如果交流輸入電源中斷,5伏總線將在規(guī)格范圍內(nèi)重新供電至少一個(gè)周期。這個(gè)然后,在SYSRESET停止所有操作之前,給系統(tǒng)額外5毫秒的時(shí)間來完成有序關(guān)機(jī)處理。
Overvoltage Protection
An electronic shutdown circuit protects against voltages exceeding 6.2 volts. A back-up voltage clamp is
provided to protect against sustained overvoltage
conditions due to either external influences or internal
faults. Overvoltage due to internal faults may cause
the fuse to open. For short term overvoltage conditions, normal operation will resume when the cause is
removed.An electronic current limit is provided on each of the
three outputs. An overload on any output will cause
the voltage to collapse and may cause the other output voltages to collapse.
Normal operation will resume after removal of the
overload. Some component cooling time may be required before normal operation resumes.Dual Rack Operation
A single power supply can provide power for two
racks under the following conditions:
Only 5 volt power is required in the second rack,
and the total power required by both racks is within the capability of the supply.
The current drawn by the second rack is less than
5.2 amperes.
The two racks must be mounted in close proximity
as limited by the available 3-foot connecting cable.
The connecting cable used for dual rack operation is
listed in Table 1, Ordering Information. This cable carries the +5 volts power bus as well as the power
sequencing signals. It uses a 9-pin D-type connector
which connects directly to the backplane through an
opening in the rack frame. Note that the cable carries
power and power sequencing signals only. Inter-rack
communication and bus interface modules must be provided separately. See the applicable Programmable
Controller Installation Manual. for application information.SYSRESET. The 5VSTBY output may be used for user
battery backup schemes as shown.
On application of power, the ACFAIL signal goes false
soon after the 5 volt bus is within specification. The system is held in the Reset state by SYSRESET for at least
200 milliseconds after 5 volt power is available (during
this time, outputs are forced off).