Vibro-meter 200-510-041-021 200-510-111-021 VM600 MPC4
Min station delay(MinTsdr)響應(yīng)方可以發(fā)送以tbits表示的響應(yīng)幀之前經(jīng)過(guò)的時(shí)間段。然而,從屬實(shí)現(xiàn)決定了最小響應(yīng)時(shí)間。默認(rèn)值為11 tbits。將MinTsdr設(shè)置得過(guò)高可能會(huì)降低性能。關(guān)閉編輯器窗口時(shí),低于11的設(shè)置將被定義的最小值11覆蓋。最大站延遲(MaxTsdr)從站響應(yīng)請(qǐng)求消息的最長(zhǎng)時(shí)間,以tbits表示。在不同的波特率下,它可能具有不同的值。自動(dòng)計(jì)算可確保主設(shè)備中設(shè)置的值高于或等于所連接從屬設(shè)備的最高值。如果沒(méi)有,將顯示警告或錯(cuò)誤消息*安靜時(shí)間(TQUI)發(fā)射站在幀結(jié)束后必須等待的時(shí)間段,然后才能啟用其接收器。其目的是在關(guān)閉變送器后注意變送器的下降時(shí)間。使用自控中繼器時(shí),這一點(diǎn)非常重要。
Min station
delay
(MinTsdr)
The period of time which elapses before the responder can send
the response frame expressed in tbits. Slave implementation
determines, however, the minimum response time. The default
value is 11 tbits. Setting MinTsdr too high may slow down the
performance. Settings below 11 will be overwritten with the defined
minimum value 11 when closing the editor window.Max station
delay
(MaxTsdr)
The maximum time the slave is given to respond to a request
message, expressed in tbits. At different baud rates it may have
different values. The automatic calculation ensures that the value
set in the master is higher or equal than the highest value for the
connected slaves. If not, a warning or error message will be
shown.
*Quiet time
(TQUI)
The period of time a transmitting station must wait after the end of
a frame before enabling its receiver. Its purpose is to take care of
transmitter fall time after switching off the transmitter. It is
significant when using self-controlled repeaters.