REOTRON 567LH-DP24驅(qū)動器模塊
刪除主機冗余如果CI854A已配置并以冗余模式運行,則可以刪除冗余。1.右鍵單擊要刪除冗余的CI854A,然后選擇冗余>刪除備份。2.圖標變?yōu)閱蝹€圖標,文本中的備份位置被刪除。配置PROFIBUS主單元硬件編輯器通過雙擊硬件單元或從CI854上下文菜單中選擇編輯器打開硬件編輯器。硬件編輯器包含以下選項卡:設(shè)置、連接和設(shè)備狀態(tài)。在Control Builder的離線模式下,M單元B始終作為備份單元顯示,與當前狀態(tài)無關(guān)。因此,B單元將始終作為備份刪除。如果您下載并聯(lián)機,如果單元B作為主要單元,則CI854A可以執(zhí)行故障切換。單元A成為主要單元,之后單元B將被刪除。
Delete Redundancy for Master Unit
If the CI854A is already configured and running in redundant mode you can delete
redundancy.
1. Right-click on the CI854A you want to delete redundancy for and select
Redundancy > Delete Backup.
2. The icon changes to the single icon and the position for the backup is deleted in
the text.
Configure the PROFIBUS Master Unit
HW Editor
Open the HW editor via double-click on the hardware unit or choose Editor from the
CI854 context menu. The HW editor contains the following tabs: Settings,
Connections and Unit Status.
In the offline mode of Control Builder M unit B is always presented as the
backup unit independent of the current state. Therefore always unit B will be
deleted as backup. If you download and go online a failover may be performed by
CI854A if unit B acts as primary. Unit A gets primary and afterwards unit B will
get deleted.