主營產(chǎn)品
PLC可編程控制器模塊,DCS卡件,ESD系統(tǒng)卡件,振動(dòng)監(jiān)測系統(tǒng)卡件,汽輪機(jī)控制系統(tǒng)模塊,燃?xì)獍l(fā)電機(jī)備件等,優(yōu)勢品牌:Allen Bradley、BentlyNevada、ABB、Emerson Ovation、Honeywell DCS、Rockwell ICS Triplex、FOXBORO、Schneider PLC、GE Fanuc、Motorola、HIMA、TRICONEX、Prosoft等各種進(jìn)口工業(yè)零部件
產(chǎn)品廣泛應(yīng)用于冶金、石油天然氣、玻璃制造業(yè)、鋁業(yè)、石油化工、煤礦、造紙印刷、紡織印染、機(jī)械、電子制造、汽車制造、塑膠機(jī)械、電力、水利、水處理/環(huán)保、鍋爐供暖、能源、輸配電等等
IS220PDIAH1B 336A5026ADP4,燃機(jī)模塊
可配置八個(gè)FUPLA功能??傋畲笾邓泄δ艿腇UPLA代碼大小為128kB。富普拉
無法復(fù)制函數(shù)。功能計(jì)劃編程工具出版物CH-ES 83-60.10 E中描述了CAP316。
控制功能取決于以下特定應(yīng)用:其是使用FUPLA特別創(chuàng)建的。它主要包括:
開關(guān)設(shè)備位置信號(hào)的檢測和合理性檢查開關(guān)設(shè)備控制
聯(lián)鎖裝置開關(guān)設(shè)備命令的監(jiān)控運(yùn)行時(shí)監(jiān)督本地模擬集成
報(bào)警和報(bào)警邏輯的檢測測量變量的處理??刂乒δ茉O(shè)置-FUPLA
重新配置FUPLA功能時(shí),目錄文件“project1.bin”和“project”。必須輸入在所有其他參數(shù)之前。文件中的項(xiàng)目名稱“project1.bin”自動(dòng)用作FUPLA的名稱
函數(shù),但名稱可以稍后更改。計(jì)時(shí)器時(shí)間因子類型的外部信號(hào)和屬于TMSEC組顯示在此窗口中。
信號(hào)可連接到以下電源:
測量變量常數(shù)設(shè)置范圍和分辨率:TMSEC信號(hào)組:0…60.000秒,用于噸0…50.00秒,對于噸
時(shí)間因子信號(hào)組:0…4000秒,用于TONL保護(hù)功能二進(jìn)制輸出(測量變量)觀察因素ms(噸)、10ms(噸)、1s(噸)。來自IBB的輸入觀察因素ms(噸)、10ms(噸)、1s(噸)。
3.6.4.1.3.二進(jìn)制輸入二進(jìn)制輸入可以連接到以下源:
始終打開(“1”)始終關(guān)閉(“0”)
二進(jìn)制系統(tǒng)輸入保護(hù)功能二進(jìn)制輸出來自IBB的輸入:24組32個(gè)信號(hào)中的786個(gè)輸入
Eight FUPLA functions can be configured. The total maximum
size of FUPLA code for all the functions is 128kB. The FUPLA
function cannot be copied. The function plan programming tool
CAP316 is described in the publication CH-ES 83-60.10 E.
The control function depends on the particular application for
which it is specifically created using FUPLA. It includes essentially:
detection and plausibility check of switchgear position signals
switchgear control
interlocks
monitoring of switchgear commands
run-time supervision
integration of the local mimic
detection of alarms and alarm logic
processing of measured variables.Control function settings - FUPLA
When reconfiguring the FUPLA function, the directory where the
files ‘project1.bin’ and ‘project.cfg’ are located must be entered
before all other parameters. The project name in the file
‘project1.bin’ is used automatically as the name of the FUPLA
function, but the name can be changed later.Timers
EXTIN signals of the time factor type and signals belonging to
the TMSEC group are displayed in this window.
The signals can be connected to the following sources
Measured variable constant
Setting range and resolution:
TMSEC signal group: 0...60.000 s, for TON
0...50.00 s, for TONS
TIMEFACTOR signal group: 0...4000 s, for TONL
Protection function binary output (measured variable)
Observe the factors ms (TON), 10 ms (TONS), 1 s (TONL).
Input from IBB
Observe the factors ms (TON), 10 ms (TONS), 1 s (TONL).
3.6.4.1.3. Binary inputs
Binary inputs can be connected to the following sources:
Always ON (“1”)
Always OFF (“0”)
Binary system inputs
Protection function binary outputs
Inputs from the IBB: 786 inputs in 24 groups of 32 signals
each.